Safety protection and protection isolating transformers for DIN bar or panel mounting

DIN rail mountable transformer 35mm

Safety protection and protection isolating transformers for DIN bar or panel mounting Transformers for DIN bar are mainly used in switchboards. High protection and modularity are their advantages.

The performance range is from 60 to 400VA.

  Type Capacity
[VA]
A
[mm]
B
[mm]
H
[mm]
E
[mm]
F
[mm]
S
[mm]
Weight
[kg]
Transformer TR9402DIN 60 90 106 87 69 90 4,5 1,1
Transformer TR9403DIN 80 90 106 96 69 90 4,5 1,6
Transformer TR9401DIN 100 90 106 106 69 90 4,5 1,9
Transformer TR9404DIN 125 90 106 116 69 90 4,5 2,3
Transformer TR9409DIN 250 126 136 117 96 121 5,5 4,4
Transformer TR9409DIN 315 126 136 127 96 121 5,5 5,3
Transformer TR9409DIN 400 126 136 117 96 121 5,5 5.3
THERMAL CLASS: E120°C
VOLTAGE WITHSTAND: PRI/SEC/CORE 4,75kV 50Hz
SHORT-CIRCUIT RESISTANCE: NOT SHORT-CIRCUIT RESISTANT
TEMPERATURE RISE (HEAT RUN): max. 85°C
PROTECTION CLASS: II.
PROTECTION: IP20
AMBIENT TEMPERATURE: ta40

Our recommendations

  • we recommend to protect the transformer with a circuit breaker as indicated on the manufacturer's label
  • based on the customer's request, we can install a thermal fuse for 130 °C - returnable