Transformers on El and Ul core
Isolation transformers

Network transformers with transformation ratio 1:1. They are used to protect against electrical shock by touching a live part, i.e. as a safety element, for example on production lines, in workshops, in laboratories, etc.
Type range: TR 9409/4 to TR 9415/4
We also produce atypical transformation ratios according to the customer's request.
| Type range | Type designation | Power [VA] | Core type DIN | Output voltage and current [V / A] | No-load losses [W] | Total losses [W] | Efficiency η [%] | |
|---|---|---|---|---|---|---|---|---|
| ∆P Cu | ∆P Fe | |||||||
| Isolating transformer | TR 9409/4 - 30 | 30 | EI 75 / 20 | 230 / 0.13 | 4 | 4.2 | 8.2 | 78 |
| Isolating transformer | TR 9409/4 - 50 | 50 | EI 75 / 25 | 230 / 0.21 | 5.6 | 6 | 11.6 | 81 |
| Isolating transformer | TR 9409/4 - 80 | 80 | EI 84 / 35 | 230 / 0.34 | 7.2 | 8.1 | 15.3 | 83 |
| Isolating transformer | TR 9409/4 - 100 | 100 | EI 84 / 40 | 230 / 0.43 | 10.4 | 8.1 | 18.5 | 84 |
| Isolating transformer | TR 9409/4 - 125 | 125 | EI 96 / 35 | 230 / 0.54 | 10.5 | 10.5 | 21 | 85 |
| Isolating transformer | TR 9409/4 - 150 | 160 | EI 96 / 45 | 230 / 0.65 | 11 | 10.5 | 21.5 | 88 |
| Isolating transformer | TR 9409/4 - 200 | 200 | EI 96 / 50 | 230 / 0.87 | 14 | 13 | 27 | 88 |
| Isolating transformer | TR 9409/4 - 250 | 250 | EI 120 / 40 | 230 / 1.08 | 15 | 16 | 31 | 88 |
| Isolating transformer | TR 9409/4 - 315 | 315 | EI 120 / 50 | 230 / 1.37 | 17 | 16 | 33 | 90 |
| Isolating transformer | TR 9409/4 - 400 | 400 | EI 120 / 70 | 230 / 1.74 | 17 | 19 | 36 | 91 |
| Isolating transformer | TR 9409/4 - 500 | 500 | EI 150 / 50 | 230 / 2.17 | 20 | 22 | 42 | 92 |
| Isolating transformer | TR 9409/4 - 800 | 800 | EI 150 / 80 | 230 / 3.47 | 25 | 28 | 53 | 93 |
| Isolating transformer | TR 9413/4 - 1000 | 1000 | EI 192 / 60 | 230 / 4.34 | 27 | 34 | 61 | 94 |
| Isolating transformer | TR 9413/4 - 1400 | 1600 | EI 192 / 80 | 230 / 6.08 | 35 | 44 | 79 | 95 |
| Isolating transformer | TR 9415/4 - 2000 | 2000 | EI 192 / 100 | 230 / 8.69 | 47 | 46 | 93 | 95 |
| Isolating transformer | TR 9415/4 - 2500 | 2500 | EI 192 / 130 | 230 / 10.86 | 61 | 50 | 111 | 95 |
| Isolating transformer | TR 9415/4 - 3 k | 3000 | UI 180 / 60 | 230 / 13.04 | 72 | 90 | 162 | 95 |
| Isolating transformer | TR 9415/4 - 4 k | 4000 | UI 180 / 80 | 230 / 17.39 | 90 | 104 | 194 | 95 |
| Isolating transformer | TR 9415/4 - 5 k | 5000 | UI 180 / 100 | 230 / 21.74 | 109 | 125 | 234 | 96 |
| Isolating transformer | TR 9415/4 - 6 k | 6300 | UI 210 / 102 | 230 / 27.4 | 130 | 156 | 286 | 96 |
| Isolating transformer | TR 9415/4 - 8 k | 8000 | UI 210 / 130 | 230 / 34.8 | 150 | 192 | 342 | 96 |
| Isolating transformer | TR 9415/4 - 10 k | 10000 | UI 210 / 130 | 230 / 43.5 | 150 | 207 | 357 | 97 |
| Isolating transformer | TR 9415/4 - 15 k | 15000 | UI 240 / 150 | 230 / 65.2 | 69 | 220 | 289 | 98 |
| THERMAL CLASS: | F 155°C |
| VOLTAGE WITHSTAND: | PRI / SEC / CORE 4,75kV 50Hz |
| SHORT-CIRCUIT RESISTANCE: | NOT SHORT-CIRCUIT RESISTANT |
| TEMPERATURE RISE (HEAT RUN): | 85 °C |
| PROTECTION CLASS: | I. |
| PROTECTION: | IP00 |
| AMBIENT TEMPERATURE: | -10 °C až + 35 °C |
Our recommendations
- protection by "T" tube fuses as indicated on the manufacturer's label
- based on the customer's request, we can install a thermal fuse for 130 °C - returnable and non-returnable
- technical changes and transformation ratios are possible based on customer requirements