Medical transformers

Transformers for medical purposes MED

They are used to supply power to medical premises, operating rooms, medical surgeries, etc. They provide electrical safety for patients and staff against electric shock, but also safe and reliable power supply in operating rooms or intensive care units.

The rooms that are powered by a medical transformer have a separate isolated network established. Medical transformers with higher performance up to 10kVA are usually used to power operating rooms or bed sections in hospitals.

In our portfolio we offer medical transformers with standard power of 1 - 10kVA with weight from 20 to 100 kg, which can be installed in electrical switchboard or outside the switchboard in a metal casing with IP23 protection. PT100 or Ptc thermistor thermal sensors are installed to monitor the temperature of the transformer. Given the important function that medical transformers have in healthcare facilities, it is recommended to purchase them from verified, reliable and certified manufacturers.

ELSIM s. r. o. is your responsible partner in the field of custom transformer manufacturing.

TYPE CAPACITY 
[VA]
TYPE Voltage
[V]
Weight
[kg]
Transformer 1000 TR 9415/4-1k 230(400) 20
Transformer 1500 TR 9415/4-1,5k 230(400) 26
Transformer 2000 TR 9415/4-2k 230(400) 30
Transformer 2500 TR 9415/4-2,5k 230(400) 32
Transformer 3150 TR 9415/4-3k 230(400) 42
Transformer 4000 TR 9415/4-4k 230(400) 48
Transformer 5000 TR 9415/4-5k 230(400) 56
Transformer 6300 TR 9415/4-6,3k 230(400) 72
Transformer 8000 TR 9415/4-8k 230(400) 82
Transformer 10000 TR 9415/4-10k 230(400) 95

Classic version: no-load current I0< 3%, short-circuit voltage uk <3% on-current <12x In

ES-Energy saving /saving version/: no-load current  I0< 2%, short-circuit voltage uk< 3% on-current <8x In

Classic version

TYPE Capacity (VA) Input voltage (V) Output voltage at Iz (V) Output current  Iz (A) ΔPFe(W) ΔPCu(W) η(%)
TR 9415/4-2,5K 2500 230 (400) 230 10,9 <45 <90 95
TR 9415/4-3K 3150 230 (400) 230 13,7 <50 <100 95
TR 9415/4-4K 4000 230 (400) 230 17,4 <55  <105 96
TR 9415/4-5K 5000 230 (400) 230 21,7 <75 <110 96
TR 9415/4-6,3K 6300 230 (400) 230 27,4 <100 <130 96
TR 9415/4-8K 8000 230 (400) 230 34,8 <105 <200 96
TR 9415/4-10K 10000 230 (400) 230 43,5 <135 <210 97

ES – Energy saving /energy-saving design/

TYPE Capacity (VA) Input voltage (V) Output voltage at Iz (V) Output current  Iz (A) ΔPFe(W) ΔPCu(W) η(%)
TR 9415/4-2,5K ES 2500 230 (400) 230 10,9 <15 <90 96
TR 9415/4-3K ES 3150 230 (400) 230 13,7 <18 <100 96
TR 9415/4-4K ES 4000 230 (400) 230 17,4 <20 <105 97
TR 9415/4-5K ES 5000 230 (400) 230 21,7 <25 <110 97
TR 9415/4-6,3K ES 6300 230 (400) 230 27,4 <34 <130 97
TR 9415/4-8K ES 8000 230 (400) 230 34,8 <40 <200 97
TR 9415/4-10K ES 10000 230 (400) 230 43,5 <42 <210 97

ΔP Fe – losses in the magnetic circuit

ΔP Cu – losses in windings

η - effectiveness

SHORT-CIRCUIT RESISTANCE: Not short-circuit resistant
PROTECTION - FUSE DII....A Gg
INPUT VOLTAGE: 230V 50Hz
PROTECTION: IP00
VOLTAGE WITHSTAND: 4700V
THERMAL CLASS: F155°C
AMBIENT TEMPERATURE: ta40

Our recommendations

  • protection by fuse gL/gG as indicated on the manufacturer's label
  • the secondary side of the transformer is with a middle tap to monitor the insulation condition
  • we install thermal sensors for control: Pt100, bi-metal 120°C, Ptc termistor
  • the rooms that are powered by the medical transformer have a separate isolated network established